Thermal Zone AC Error Codes and Troubleshooting

 This air conditioning system has been provided with built in self diagnostic error codes. Please refer to the following table for error code definitions:

Thermal Zone AC Error Codes and Troubleshooting
Error CodesMalfunction Name
H4System Overload. Heating LED: 4 Flashes
H3Compressor Overload Protection. Heating LED: 3 Flashes
H5 IPM Protection. Heating LED: 5 Flashes
E1 High Pressure Protection. Running LED: 1 Flash
E2 Anti-Freezing Protection. Running LED: 2 Flashes
E4 Exhaust Protection. Running LED: 4 Flashes
E5 Over Current Protection. Running LED: 5 Flashes
E7Mode Conflict. Running LED: 7 Flashes
E6Communication Malfunction. Running LED: 6 Flashes
H1Defrost or Oil Return of Heat. Heating LED: 1 Flash
F1 Indoor Ambient Sensor Malfunction. Cooling LED: 1 Flash
F2 Indoor Tube Sensor Malfunction. Cooling LED: 2 Flashes
F3Outdoor Ambient Sensor Malfunction. Cooling LED: 3 Flashes
F4Outdoor Tube Sensor Malfunction. Cooling LED: 4 Flashes
F5Outdoor Exhaust Sensor Malfunction. Cooling LED: 5 Flashes
 H7 Failure Startup. Heating LED: 7 Flashes
HC PFC Malfunction PFC. Heating LED: 6 Flashes
HEDemagnetizing Protection for Compressor. Heating LED: 14 Flashes
F6 Frequency Drop for Overload. Cooling LED: 6 Flashes
F8 Frequency Drop for Over Current Protection. Cooling LED: 8 Flashes
F9Frequency Drop for Exhaust Protection. Cooling LED: 9 Flashes
H0Frequency Drop for Heating High Temperature Protection. Heating LED: 10 Flashes
E9Anti-Cold Protection. Running LED: 9 Flashes
F7Oil Return of Cooling. Cooling LED: 7 Flashes

Troubleshooting

Thermal Zone Mini-split Troubleshooting Guide
Thermal Zone Mini-split Troubleshooting Guide

The first step in troubleshooting is to disconnect power for 30 seconds to allow the unit to reset. If this does not rectify the problem proceed with the troubleshooting chart below.

Problem: The unit does not run.

Troubleshooting:

  1. Is the power off?
  2. Is the circuit protection device tripped?
  3. Is voltage too high or low? (Tested by a professional)
  4. Is the Timer on?
  5. A 3 minute delay occurs before each compressor start.

Problem: Cooling and or Heating efficiency is not good.

Troubleshooting:

  1. Is temperature setting correct?
  2. Are the inlet or outlet vents obstructed?
  3. Is the filter clean?
  4. Are windows and doors closed?
  5. Is fan set to low speed?
  6. Is there a heat source in the room?

Problem: Wireless remote control is not working.

Troubleshooting:

  1. Reset unit. Disconnect main power for 30 seconds then reapply.
  2. Is it within receiving range? Is it obstructed?
  3. Replace the batteries.
  4. Is remote control damaged?

Problem: Water leaking into room.

Troubleshooting:

  1. The air humidity is excessively high. Check to see if all windows and doors are closed.
  2. Call service Tech if not corrected by the above action.

Problem: Water leakage in outdoor unit.

Troubleshooting:

  1. When the unit is running in Auto Defrosting mode, ice will thaw and drip into pan.
  2. When the unit is running in HEAT mode, the water adhered to the condenser coil drains into pan.

Problem: Noise from indoor unit emitted.

Troubleshooting:

  1. When defrosting is started or stopped, it will make a sound. This is due to the refrigerant flow reversing directions.
  2. Normal refrigerant flowing in unit.

Notes: 

  1. If E7 error code occurs, see the AUTO mode section in Operators Manual on page 7 .
  2. An audible beep will be heard, when a button is pressed, if the remote control is communicating with the receiver.
Thermal Zone AC - Name and Function of each Part
Thermal Zone AC – Name and Function of each Part

Thermal Zone Air Conditioner Manual

Thermal Zone Mini-split Air Conditioning Systems PDF

Comments

Popular posts from this blog

Rittal Air Conditioner Error Codes

  System messages are shown on the display screen of the Comfort controller via the displays A1 to A20 and E0. Rittal Air Conditioner Error Codes Error Codes System message Possible cause A1 Enclosure door open Door open or door limit switch incorrectly positioned A2 Internal temperature of enclosure too high Cooling capacity inadequate/unit undersized. Error as a consequence of messages A03 to A17. A3 Filter monitoring Filter mat soiled A4 Ambient temperature too high/too low Ambient temperature outside of admissible operating range (+10°C to +60°C) A5 Icing hazard Operational display in case of icing hazard. A6 PSAH pressure-operated switch Ambient temperature too high A7 Evaporator coil Lack of coolant; sensor in front of or behind condenser defective. A8 Condensate warning Condensate discharge kinked or blocked A9 Condenser fan blocked or defective Blocked or defective A10 Evaporator fan blocked or defective Blocked or defective A11 Compressor Compressor overloaded A12 Condense...

Samsung DVM-S VRF Error Codes

  DVM Digital Variable Multi VRF Systems Error Codes Samsung DVM VRF Error Codes Error code related indoor unit: Error Codes Explanation E-101 Indoor unit communication error. Indoor unit can not receive any data from outdoor unit. E-102 Communication error between indoor unit and outdoor unit. Displayed in indoor unit. E-108 Error due to repeated address setting (When 2 or more devices has same address within the network) E-121 Error on indoor temperature sensor of indoor unit (Short or Open) E-122 Error on EVA IN sensor of indoor unit (Short or Open) E-123 Error on EVA OUT sensor of indoor unit (Short or Open) E-128 EVA IN temperature sensor of indoor unit is detached from EVA IN pipe E-129 EVA OUT temperature sensor of indoor unit is detached from EVA OUT pipe E-130 Heat exchanger in/out sensors of indoor unit are detached E-135 RPM feedback error of indoor unit's cleaning fan E-149 Error due to AHU master indoor unit sensor setting. E-151 Error due to opened EEV of indoor unit ...

Panasonic VRF AC Error Codes and Troubleshooting

  Indoor unit is detecting error signal from remote controller (and system controller). Panasonic Mini VRF AC Error Codes and Troubleshooting Error Codes Meaning E01 Error in receiving serial communication signal. E02 Error in transmitting serial communication signal. E03 Indoor unit is detecting error signal from remote controller. E04 Error in receiving serial communication signal. When turning on the power supply, the number of connected indoor units does not correspond to the number set. E06 Error of the outdoor unit in receiving serial communication signal from the indoor unit. E08 Indoor unit address setting is duplicated. E09 Remote controller address connector. E12 Starting auto address setting is prohibited. This alarm message shows that the auto address connector CN-A.ADD is shorted while other RC line is executing auto address operation. E15 Error in auto address setting. E16 Error in auto address setting. E20 No indoor unit is connected during auto address setting. E24 ...