Rittal Air Conditioner Error Codes

 System messages are shown on the display screen of the Comfort controller via the displays A1 to A20 and E0.

Rittal Air Conditioner Error Codes
Rittal Air Conditioner Error Codes

Rittal AC Fault Indication and Fault Analysis:

Rittal Air Conditioner Device Description
Rittal Air Conditioner Device Description

Fault: 1

Cause: Cooling output too low (lack of coolant) Consequential fault or faults 2-7. Remedy: Check cooling output Carry out cooling service.

Fault: 2 Cause: Compressor overloaded (internal winding protection). Remedy: Unit will switch on automatically.

Fault: 3 Cause: Operational indication if risk of icing up exists. Remedy: Raise the setpoint value of the internal temperature of enclosure.

Fault: 4 Cause: Ambient temperature too high. Remedy: Unit’s specified range of application exceeded

Fault: 5 Cause: Blocked or defective. Remedy: Replace.

Fault: 6 Cause: Blocked or defective. Remedy: Replace.

Fault: 7

Cause: Filter mat contaminated. Remedy: Clean or replace.

Fault: 8 Cause: Cable break or short-circuit. Remedy: Replace.

Fault: 9 Cause: Incorrect field of rotation. Remedy: Reverse two phases.

Troubleshooting

Rittal AC Control Using the Comfort Controller
Rittal AC Control Using the Comfort Controller

Trouble: The unit does not switch on.

Possible Cause: No power supply.

Correction: Check the mains connection and the pre-fuse.

Trouble: The unit does not cool/heat adequately.

Possible Cause:

  1. The air circulation inside the enclosure is impaired.
  2. Ambient temperature too high/low.
  3. Filter equipment contaminated.
  4. Internal fan defective.
  5. External fan defective.
  6. The heat produced in the enclosure exceeds the cooling capacity of the Peltier climate control unit.

Correction:

  1. Check the air circulation inside the enclosure. Check, in particular, those components equipped with a fan. Check the free spaces above and below the main heat dissipation sources.
  2. Reduce the ambient temperature. Protect the unit from radiation heat caused by direct sunshine and hot surfaces.
  3. Check the filter and, if necessary, clean or replace.
  4. Replace unit.
  5. Replace unit.
  6. Reduce the heat loss.

Trouble: Condensation.

Possible Cause:

  1. Enclosure leakages.
  2. Internal temperature of enclosure set too low.

Correction:

  1. Check the enclosure for leaks (IP 54). Check, in particular, the cable entry points for leaks.
  2. Check the set enclosure internal temperature (factory setting: +35°C).

Rittal Air Conditioner Manual PDF

Comments

Popular posts from this blog

AUX Air Con Error Codes

Aux Air Conditioner Troubleshooting November 3, 2018 at 9:18 pm If the following phenomena are found, the problem is not from the  air-conditioner itself. Problems The motor is heard operating but the air-conditioner dose not work when the indoor unit is powered on Causes Since the air-conditioner is powered on, it will come to working condition as long as you press the ON/OFF button of the remote control and the Signal is well received. Problems The compressor stops running but the indoor fan motor keeps working when it is at cooling mode with the indoor temperature higher than set temperature. Causes If you turn off the air-conditioner and restart it immediately, it will return to normal in 3 minutes, after that, the air-conditioner will automatically adjust the indoor fan speed to what you set. Problems The compressor works discontinuously at dehumidifying mode. Causes The air-conditioner will automatically control the working of the compressor according to the insi

Acson AC Error Codes and Troubleshooting

Acson AC Error Codes and Troubleshooting   The code indication changes as shown below, and notifies with a long beep. Wall Mounted AC Inverter Unit Error Codes Operation / Faulty Indication E1 Room air sensor contact loose / short. Check room sensor connection / change room sensor E2 Indoor coil sensor contact open. Check indoor coil sensor connection / change indoor coil sensor E3 Outdoor coil sensor contact open. Check outdoor coil sensor connection / change outdoor coil sensor E4 Compressor overload protection / Indoor / Outdoor coil sensor short. If running ampere highly increase, change the compressor. If not, replace the coil sensor E5 Gas leak. Check for leakage & repair / Top up refrigerant E6 Pump fault. Clear the clogging at drain pipe. If pump is not working, change the pump E7 Outdoor coil sensor exist (MS model). Remove outdoor coil sensor E8 Hardware error (tact switch pin short). Check for the tact switch pin condition E9 No Feedback from indoor fan. Check indoor fan