 System messages are shown on the display screen of the Comfort controller via the displays A1 to A20 and E0.

Rittal Air Conditioner Error Codes
Rittal Air Conditioner Error Codes

Rittal AC Fault Indication and Fault Analysis:

Rittal Air Conditioner Device Description
Rittal Air Conditioner Device Description

Fault: 1

Cause: Cooling output too low (lack of coolant) Consequential fault or faults 2-7. Remedy: Check cooling output Carry out cooling service.

Fault: 2 Cause: Compressor overloaded (internal winding protection). Remedy: Unit will switch on automatically.

Fault: 3 Cause: Operational indication if risk of icing up exists. Remedy: Raise the setpoint value of the internal temperature of enclosure.

Fault: 4 Cause: Ambient temperature too high. Remedy: Unit’s specified range of application exceeded

Fault: 5 Cause: Blocked or defective. Remedy: Replace.

Fault: 6 Cause: Blocked or defective. Remedy: Replace.

Fault: 7

Cause: Filter mat contaminated. Remedy: Clean or replace.

Fault: 8 Cause: Cable break or short-circuit. Remedy: Replace.

Fault: 9 Cause: Incorrect field of rotation. Remedy: Reverse two phases.

Troubleshooting

Rittal AC Control Using the Comfort Controller
Rittal AC Control Using the Comfort Controller

Trouble: The unit does not switch on.

Possible Cause: No power supply.

Correction: Check the mains connection and the pre-fuse.

Trouble: The unit does not cool/heat adequately.

Possible Cause:

  1. The air circulation inside the enclosure is impaired.
  2. Ambient temperature too high/low.
  3. Filter equipment contaminated.
  4. Internal fan defective.
  5. External fan defective.
  6. The heat produced in the enclosure exceeds the cooling capacity of the Peltier climate control unit.

Correction:

  1. Check the air circulation inside the enclosure. Check, in particular, those components equipped with a fan. Check the free spaces above and below the main heat dissipation sources.
  2. Reduce the ambient temperature. Protect the unit from radiation heat caused by direct sunshine and hot surfaces.
  3. Check the filter and, if necessary, clean or replace.
  4. Replace unit.
  5. Replace unit.
  6. Reduce the heat loss.

Trouble: Condensation.

Possible Cause:

  1. Enclosure leakages.
  2. Internal temperature of enclosure set too low.

Correction:

  1. Check the enclosure for leaks (IP 54). Check, in particular, the cable entry points for leaks.
  2. Check the set enclosure internal temperature (factory setting: +35°C).

Rittal Air Conditioner Manual PDF

Comments

Popular posts from this blog

Vestel AC Error Codes and Troubleshooting

  Error Messages   are displayed, respectively by first the   Er   icon and then the special code (01, 02, …, 20, etc.) of the failure. In that case, do nothing to the air conditioner and contact with the Authorised Service.   Er11   and   Er13   are not error messages. If you see these messages, apply the steps under the following protection messages section. Vestel AC Error Code and Troubleshooting Error Codes Cause dF The icing on the outdoor unit is being defrosted. After the defrosting operation is accomplished, your air conditioner will continue to operate in the heating mode, the product should not be turned off while this mode is enabled. RE Make the arc control for your electrical wiring, if the problem is not fixed call for the service. If the problem comes out very frequently, contact with the authorised service. Sr In case of certain failures, in order to not to spoil you comfort, your air conditioner continues to operate despite the f...

Panasonic VRF AC Error Codes and Troubleshooting

  Indoor unit is detecting error signal from remote controller (and system controller). Panasonic Mini VRF AC Error Codes and Troubleshooting Error Codes Meaning E01 Error in receiving serial communication signal. E02 Error in transmitting serial communication signal. E03 Indoor unit is detecting error signal from remote controller. E04 Error in receiving serial communication signal. When turning on the power supply, the number of connected indoor units does not correspond to the number set. E06 Error of the outdoor unit in receiving serial communication signal from the indoor unit. E08 Indoor unit address setting is duplicated. E09 Remote controller address connector. E12 Starting auto address setting is prohibited. This alarm message shows that the auto address connector CN-A.ADD is shorted while other RC line is executing auto address operation. E15 Error in auto address setting. E16 Error in auto address setting. E20 No indoor unit is connected during auto address setting. E24 ...