Ruud AC Error Codes and Troubleshooting

 

Ruud AC Error Codes and Troubleshooting
Ruud AC Error Codes and Troubleshooting

Warning; Disconnect all power to unit before servicing. contactor may break only one side. Failure to shut off power can cause electrical shock resulting in personal injury or death.

Comfort Alert Diagnosis Chart Single Phase Unit

Status LED: Green “POWER”

Status LED Description: Module has power

Status LED Troubleshooting Information: Supply voltage is present at module terminals

Status LED: Red “TRIP”

Status LED Description: Thermostat demand signal Y1 is present, but the compressor is not running

Status LED Troubleshooting Information:

  1. Compressor internal overload is open
  2. Broken wire or connector is not making contact
  3. Low pressure switch open, if present
  4. Compressor contactor has failed open

Status LED: Yellow “ALERT” Flash Code 1

Status LED Description: Long Run Time Compressor is running extremely long run cycles

Status LED Troubleshooting Information:

  1. Low refrigerant charge
  2. Evaporator blower is not running
  3. Evaporator coil is frozen
  4. Faulty TXV
  5. Condenser coil is dirty
  6. Liquid line restriction (filter drier blocked if present in system)
  7. Thermostat is malfunctioning

Status LED: Yellow “ALERT” Flash Code 2

Status LED Description: System Pressure Trip Discharge or suction pressure out of limits or compressor overloaded

Status LED Troubleshooting Information:

  1. Condenser coil poor air circulation (dirty, blocked, damaged)
  2. Condenser fan is not running
  3. Return air duct has substantial leakage
  4. If low pressure switch is present, check flash code (1) information

Status LED: Yellow “ALERT” Flash Code 3

Status LED Description: Short Cycling Compressor is running only briefly

Status LED Troubleshooting Information:

  1. High head pressure
  2. Thermostat demand signal is intermittent
  3. Time delay relay defective, if present
  4. Hot gas sensor defective, if present

Status LED: Yellow “ALERT” Flash Code 4 

Status LED Description: Locked Rotor

Status LED Troubleshooting Information:

  1. Run capacitor has failed
  2. Low line voltage (contact utility if voltage at disconnect is low)
  3. Excessive liquid refrigerant in compressor
  4. Compressor bearings are seized

Status LED: Yellow “ALERT” Flash Code 5

Status LED Description: Open Circuit

Status LED Troubleshooting Information:

  1. Compressor contactor has failed open
  2. High pressure switch is open, If present
  3. Open circuit in compressor supply wiring or connections
  4. Unusually long compressor protector reset time due to extreme ambient temperature
  5. Compressor windings are damaged

Status LED: Yellow “ALERT” Flash Code 6

Status LED Description: Open Start Circuit Current only in run circuit

Status LED Troubleshooting Information:

  1. Run capacitor has failed
  2. Open circuit in compressor start wiring or connections
  3. Compressor start winding is damaged

Status LED: Yellow “ALERT” Flash Code 7

Status LED Description: Open Run Circuit Current only in start circuit

Status LED Troubleshooting Information:

  1. Open circuit in compressor run wiring or connections
  2. Compressor run winding is damaged

Status LED: Yellow “ALERT” Flash Code 8

Status LED Description: Welded Contactor Compressor always runs

Status LED Troubleshooting Information:

  1. Compressor contactor has failed closed
  2. Thermostat demand signal not connected to module

Status LED: Yellow “ALERT” Flash Code 9 

Status LED Description: Low Voltage Control circuit < 17VAC

Status LED Troubleshooting Information:

  1. Control circuit transformer is overloaded
  2. Low line voltage (contact utility if voltage at disconnect is low)

Ruud Air Conditioner Troubleshooting

Ruud-Air-Conditioners-Troubleshooting
Ruud Air Conditioners Troubleshooting

Symptom: Unit will not run

Possible Cause:

  1. Power off or loose electrical connection
  2. Thermostat out of calibration-set too high
  3. Defective contactor
  4. Blown fuses
  5. Transformer defective
  6. High pressure control open (if provided)
  7. Interconnecting low voltage wiring damaged

Remedy:

  1. Check for correct voltage at compressor contactor in control box
  2. Reset
  3. Check for 24 volts at contactor coil – replace if contacts are open
  4. Replace fuses
  5. Check wiring-replace transformer
  6. Reset-also see high head pressure remedy-The high pressure control opens at 610 PSIG
  7. Replace thermostat wiring

Symptom: Condenser fan runs, compressor doesn’t

Possible Cause:

  1. Run or start capacitor defective (single phase only)
  2. Start relay defective (single phase only)
  3. Loose connection
  4. Compressor stuck, grounded or open motor winding. open internal overload
  5. Low voltage condition
  6. Low voltage condition

Remedy:

  1. Replace
  2. Replace
  3. Check for correct voltage at compressor – check & tighten all connections
  4. Wait at least 2 hours for overload to reset. If still open, replace the compressor.
  5. At compressor terminals, voltage must be within 10% of rating plate volts when unit is operating.
  6. Add start kit components.

Symptom: Insufficient cooling

Possible Cause:

  1. Improperly sized unit
  2. Improper airflow
  3. Incorrect refrigerant charge
  4. Air, non-condensibles or moisture in system
  5. Incorrect voltage

Remedy:

  1. Recalculate load
  2. Check – should be approximately 400 CFM per ton.
  3. Charge per procedure attached to unit service panel
  4. Recover refrigerant, evacuate & recharge, add filter drier
  5. At compressor terminals, voltage must be within 10% of rating plate volts when unit is operating.

Symptom: Compressor short cycles

Possible Cause:

  1. Incorrect voltage
  2. Defective overload protector
  3. Refrigerant undercharge

Remedy:

  1. At compressor terminals, voltage must be ± 10% of nameplate marking when unit is operating.
  2. Replace – check for correct voltage
  3. Add refrigerant

Symptom: Registers sweat

Possible Cause: Low evaporator airflow

Remedy: Increase speed of blower or reduce restriction – replace air filter

Symptom: High head-low vapor pressures

Possible Cause:

  1. Restriction in liquid line, expansion device or filter drier
  2. Flow check piston size too small
  3. Incorrect capillary tubes
  4. TXV does not open

Remedy:

  1. Remove or replace defective component
  2. Change to correct size piston
  3. Change coil assembly
  4. Replace TXV

Symptom: High head-high or normal vapor pressure – Cooling mode

Possible Cause:

  1. Dirty condenser coil
  2. Refrigerant overcharge
  3. Condenser fan not running
  4. Air or non-condensibles in system

Remedy:

  1. Clean coil
  2. Correct system charge
  3. Repair or replace
  4. Recover refrigerant, evacuate & recharge

Symptom: Low head-high vapor pressures

Possible Cause:

  1. Flow check piston size too large
  2. Defective Compressor valves
  3. Incorrect capillary tubes

Remedy:

  1. Change to correct size piston
  2. Replace compressor
  3. Replace coil assembly

Symptom: Low vapor – cool compressor – iced evaporator coil

Possible Cause:

  1. Low evaporator airflow
  2. Operating below 65°F outdoors
  3. Moisture in system
  4. TXV limiting refrigerant flow

Remedy:

  1. Increase speed of blower or reduce restriction – replace air filter
  2. Add Low Ambient Kit
  3. Recover refrigerant – evacuate & recharge – add filter drier
  4. Replace TXV

Symptom: High vapor pressure

Possible Cause:

  1. Excessive load
  2. Defective compressor

Remedy:

  1. Recheck load calculation
  2. Replace

Symptom: Fluctuating head & vapor pressures

Possible Cause:

  1. TXV hunting
  2. Air or non-condensibles in system

Remedy:

  1. Check TXV bulb clamp – check air distribution on coil – replace TXV
  2. Recover refrigerant, evacuate & recharge

Symptom: Gurgle or pulsing noise at expansion device or liquid line

Possible Cause: Air or non-condensibles in system

Remedy: Recover refrigerant, evacuate & recharge

Wiring Diagram

APM-018 WITH ECM FAN MOTOR
APM-018 WITH ECM FAN MOTOR
For Single-Phase Models
For Single-Phase Models
For Three-Phase Models
For Three-Phase Models

Ruud Air Conditioners  Manual PDF

 

Comments

Popular posts from this blog

Rittal Air Conditioner Error Codes

  System messages are shown on the display screen of the Comfort controller via the displays A1 to A20 and E0. Rittal Air Conditioner Error Codes Error Codes System message Possible cause A1 Enclosure door open Door open or door limit switch incorrectly positioned A2 Internal temperature of enclosure too high Cooling capacity inadequate/unit undersized. Error as a consequence of messages A03 to A17. A3 Filter monitoring Filter mat soiled A4 Ambient temperature too high/too low Ambient temperature outside of admissible operating range (+10°C to +60°C) A5 Icing hazard Operational display in case of icing hazard. A6 PSAH pressure-operated switch Ambient temperature too high A7 Evaporator coil Lack of coolant; sensor in front of or behind condenser defective. A8 Condensate warning Condensate discharge kinked or blocked A9 Condenser fan blocked or defective Blocked or defective A10 Evaporator fan blocked or defective Blocked or defective A11 Compressor Compressor overloaded A12 Condense...

Samsung DVM-S VRF Error Codes

  DVM Digital Variable Multi VRF Systems Error Codes Samsung DVM VRF Error Codes Error code related indoor unit: Error Codes Explanation E-101 Indoor unit communication error. Indoor unit can not receive any data from outdoor unit. E-102 Communication error between indoor unit and outdoor unit. Displayed in indoor unit. E-108 Error due to repeated address setting (When 2 or more devices has same address within the network) E-121 Error on indoor temperature sensor of indoor unit (Short or Open) E-122 Error on EVA IN sensor of indoor unit (Short or Open) E-123 Error on EVA OUT sensor of indoor unit (Short or Open) E-128 EVA IN temperature sensor of indoor unit is detached from EVA IN pipe E-129 EVA OUT temperature sensor of indoor unit is detached from EVA OUT pipe E-130 Heat exchanger in/out sensors of indoor unit are detached E-135 RPM feedback error of indoor unit's cleaning fan E-149 Error due to AHU master indoor unit sensor setting. E-151 Error due to opened EEV of indoor unit ...

Panasonic VRF AC Error Codes and Troubleshooting

  Indoor unit is detecting error signal from remote controller (and system controller). Panasonic Mini VRF AC Error Codes and Troubleshooting Error Codes Meaning E01 Error in receiving serial communication signal. E02 Error in transmitting serial communication signal. E03 Indoor unit is detecting error signal from remote controller. E04 Error in receiving serial communication signal. When turning on the power supply, the number of connected indoor units does not correspond to the number set. E06 Error of the outdoor unit in receiving serial communication signal from the indoor unit. E08 Indoor unit address setting is duplicated. E09 Remote controller address connector. E12 Starting auto address setting is prohibited. This alarm message shows that the auto address connector CN-A.ADD is shorted while other RC line is executing auto address operation. E15 Error in auto address setting. E16 Error in auto address setting. E20 No indoor unit is connected during auto address setting. E24 ...