OLMO AC Error Codes and Troubleshooting

 Scandic and Tropic Series

When below list for identification of error code occurs, please turn off air conditioner and disconnect power, and then contact the qualified professionals for service.

OLMO Mini Split AC Error Codes and Troubleshooting
OLMO AC Error Codes and Troubleshooting
Error CodeTroubleshooting
E0Indoor unit EEPROM parameter error
E1Indoor / outdoor units communication error
E2Zero-crossing signal detection error
E3Indoor fan speed has been out of control
E4Indoor room temperature sensor T1 open circuit or short circuit
E5Evaporator coil temperature sensor T2 open circuit or short circuit
ECRefrigerant leakage detection
F1Outdoor temperature sensor T4 open circuit or short circuit
F2Condenser coil temperature sensor T3 open circuit or short circuit
F3Compressor discharge temperature sensor T5 open circuit or short circuit
F4Outdoor unit EEPROM parameter error
F5Outdoor fan speed has been out of control
P0IPM malfunction or IGBT over-strong current protection
P1Over voltage or over low voltage protection
P2High temperature protection of compressor top diagnosis and solution
P4Inverter compressor drive error

Troubleshooting

OLMO AC Troubleshooting
OLMO AC Troubleshooting

Before calling for service, review this list. It may save your time and expense. This list includes common occurrences that are not the result of defective workman-ship or materials in this appliance.

ProblemSolution
Air conditioner does not startWall plug disconnected. Push plug firmly into wall outlet.
House fuse blown or circuit breaker tripped. Replace fuse with time delay type or reset circuit breaker.
Plug Current Device Tripped. Press the RESET button.
Power is OFF. Turn power ON.
Air from unit does not feel cold enoughRoom temperature below 62 F(17 C ). Cooling may not occur until room temperature O O rises above 62 F(17 C).
Temperature sensing behind air filter element touching cold coil. Keep it from the cold coil.
Set to a Lower temperature.
Compressor stopped when changing modes. Wait for 3 minutes after set to the COOL mode.
Air conditioner cooling, but room is too warm- ice forming on cooling coil behind decorative front.Outdoor temperature below 64 F(18 C). To defrost the coil, set FAN ONLY mode.
Air filter may be dirty. Clean filter. Refer to Care and Cleaning section. To defrost, set to FAN ONLY mode.
Thermostat set too cold for night-time cooling. To defrost the coil, set to FAN ONLY mode. Then, set temperature to a Higher setting.
Air conditioner cooling, but room is too warm- NO ice forming on cooling coil behind decorative front.Dirty air filter- air restricted. Clean air filter. Refer to Care and Cleaning section.
Temperature is set too High, set temperature to a Lower setting.
Air directional louvers positioned improperly. Position louvers for better air distribution.
Front of units is blocked by drapes, blinds, furniture, etc. - restricts air distribution. Clear blockage in front of unit.
Doors, windows, registers, etc. Open- cold air escapes. Close doors, windows, registers.
Unit recently turned on in hot room. Allow additional time to remove Stored heat from walls, ceiling, floor and furniture.
Air conditioner turns on and off rapidlyDirty air filter- air restricted. Clean air filter.
Outside temperature extremely hot. Set FAN speed to a Higher setting to bring air past cooling coils more frequently
Noise when unit is coolingAir movement sound. This is normal . If too loud, set to a slower FAN setting
Window vibration - poor installation. Refer to installation instructions or check with installer.
Water dripping INSIDE when unit is cooling.Improper installation. Tilt air conditioner slightly to the outside to allow water drainage. Refer to installation instructions - check with installer.
Water dripping OUTSIDE when unit is cooling.Unit removing large quantity of moisture from humid room. This is normal during excessively humid days.
Remote Sensing Deactivating Prematurely (some models)Remote control not located within range. Place remote control within 20 feet & 180 , radius of the front of the unit.
Remote control signal obstructed. Remove obstruction.
Room too coldSet temperature too low. Increase set temperature.
OLMO Air Conditioner Remote Control
OLMO Air Conditioner Remote Control

Diagnosis and Solution

EEPROM parameter error diagnosis and solution (E0/F4)

Malfunction decision conditions: Indoor or outdoor PCB main chip does not receive feedback from EEPROM chip.

Supposed causes:

  • Installation mistake
  • PCB faulty

Indoor / outdoor unit’s communication diagnosis and solution (E1)

Malfunction decision conditions: Indoor unit does not receive the feedback from outdoor unit during 110 seconds and this condition happens four times continuously.

Supposed causes:

  • Wiring mistake
  • Indoor or outdoor PCB faulty

Zero crossing detection error diagnosis and solution (E2)

Malfunction decision conditions: When PCB does not receive zero crossing signal feedback for 4 minutes or the zero crossing signal time interval is abnormal.

Supposed causes:

  • Connection mistake
  • PCB faulty
OLMO Air Conditioner Remote Control Display
OLMO Air Conditioner Remote Control Display

Fan speed has been out of control diagnosis and solution (E3)

Malfunction decision conditions: When indoor fan speed keeps too low (300RPM) for certain time, the unit will stop and the LED will display the failure.

Supposed causes:

  • Wiring mistake
  • Fan ass’y faulty
  • Fan motor faulty
  • PCB faulty

Open circuit or short circuit of temperature sensor diagnosis and solution (E5)

Malfunction decision conditions: If the sampling voltage is lower than 0.06V or higher than 4.94V, the LED will display the failure.

Supposed causes:

  • Wiring mistake
  • Sensor faulty

Refrigerant Leakage Detection diagnosis and solution (EC)

Malfunction decision conditions: Define the evaporator coil temp.T2 of the compressor just starts running as Tcool. In the beginning 5 minutes after the compressor starts up, if T2 < Tcool 28.4o F(-2o C) does not keep continuous 4 seconds and this situation happens 3 times, the display area will show “EC” and AC will turn off.

Supposed causes:

  • T2 sensor faulty
  • Indoor PCB faulty
  • System problems, such as leakage or blocking.

IPM malfunction or IGBT over-strong current protection diagnosis and solution (P0)

Malfunction decision conditions: When the voltage signal that IPM send to compressor drive chip is abnormal, the display LED will show “P0” and AC will turn off.

Supposed causes: Wiring mistake; IPM malfunction; Outdoor fan ass’y faulty Compressor malfunction; Outdoor PCB faulty

Over voltage or too low voltage protection diagnosis and solution (P1)

Malfunction decision conditions: An abnormal voltage rise or drop is detected by checking the specified voltage detection circuit.

Supposed causes:

  • Power supply problems.
  • System leakage or block

High temperature protection of compressor top diagnosis and solution (P2)

Malfunction decision conditions: If the sampling voltage is not 5V, the LED will display the failure.

Supposed causes:

  • Power supply problems.
  • System leakage or block

Inverter compressor drive error diagnosis and solution (P4)

Malfunction decision conditions: An abnormal inverter compressor drive is detected by a special detection circuit, including communication signal detection, voltage detection, compressor rotation speed signal detection and so on.

Supposed causes: Wiring mistake; IPM malfunction; Outdoor fan ass’y faulty Compressor malfunction; Outdoor PCB faulty

OLMO Air Conditioner Manual PDF

Comments

Popular posts from this blog

Rittal Air Conditioner Error Codes

  System messages are shown on the display screen of the Comfort controller via the displays A1 to A20 and E0. Rittal Air Conditioner Error Codes Error Codes System message Possible cause A1 Enclosure door open Door open or door limit switch incorrectly positioned A2 Internal temperature of enclosure too high Cooling capacity inadequate/unit undersized. Error as a consequence of messages A03 to A17. A3 Filter monitoring Filter mat soiled A4 Ambient temperature too high/too low Ambient temperature outside of admissible operating range (+10°C to +60°C) A5 Icing hazard Operational display in case of icing hazard. A6 PSAH pressure-operated switch Ambient temperature too high A7 Evaporator coil Lack of coolant; sensor in front of or behind condenser defective. A8 Condensate warning Condensate discharge kinked or blocked A9 Condenser fan blocked or defective Blocked or defective A10 Evaporator fan blocked or defective Blocked or defective A11 Compressor Compressor overloaded A12 Condense...

Samsung DVM-S VRF Error Codes

  DVM Digital Variable Multi VRF Systems Error Codes Samsung DVM VRF Error Codes Error code related indoor unit: Error Codes Explanation E-101 Indoor unit communication error. Indoor unit can not receive any data from outdoor unit. E-102 Communication error between indoor unit and outdoor unit. Displayed in indoor unit. E-108 Error due to repeated address setting (When 2 or more devices has same address within the network) E-121 Error on indoor temperature sensor of indoor unit (Short or Open) E-122 Error on EVA IN sensor of indoor unit (Short or Open) E-123 Error on EVA OUT sensor of indoor unit (Short or Open) E-128 EVA IN temperature sensor of indoor unit is detached from EVA IN pipe E-129 EVA OUT temperature sensor of indoor unit is detached from EVA OUT pipe E-130 Heat exchanger in/out sensors of indoor unit are detached E-135 RPM feedback error of indoor unit's cleaning fan E-149 Error due to AHU master indoor unit sensor setting. E-151 Error due to opened EEV of indoor unit ...

Panasonic VRF AC Error Codes and Troubleshooting

  Indoor unit is detecting error signal from remote controller (and system controller). Panasonic Mini VRF AC Error Codes and Troubleshooting Error Codes Meaning E01 Error in receiving serial communication signal. E02 Error in transmitting serial communication signal. E03 Indoor unit is detecting error signal from remote controller. E04 Error in receiving serial communication signal. When turning on the power supply, the number of connected indoor units does not correspond to the number set. E06 Error of the outdoor unit in receiving serial communication signal from the indoor unit. E08 Indoor unit address setting is duplicated. E09 Remote controller address connector. E12 Starting auto address setting is prohibited. This alarm message shows that the auto address connector CN-A.ADD is shorted while other RC line is executing auto address operation. E15 Error in auto address setting. E16 Error in auto address setting. E20 No indoor unit is connected during auto address setting. E24 ...