Gree Chiller Error Code List

 Gree Water-Cooled Screw Chiller

Gree Chiller Error Code List
Gree Chiller Error Code List

Error Display: high pressure of compressor

Name: high pressure protection

Source of Error Signal: high pressure switch

Description: When the high temperature of system exceeds the setting value, the high pressure protection occurs and the corresponding malfunction LED lights while the compressor stops immediately. The malfunction information is shown on the wired controller. The unit can be started up only after the malfunction is removed manually.

Error Display: low pressure of compressor 

Name: low pressure protection

Source of Error Signal: low pressure switch

Description: When the low temperature of system is lower than the setting value, the low pressure protection occurs and the corresponding malfunction LED lights while the compressor stops immediately. The malfunction information is shown on the wired controller. The unit can be started up only after the malfunction is removed manually.

Error Display: overload of compressor 

Name: overload protection

Source of Error Signal: thermal relay

Description: Upon overcurrent of compressor, the overload protection will occur and the corresponding malfunction LED lights while the compressor stops immediately. The malfunction information is shown on the wired controller. The unit can be started up only after the malfunction is removed manually.

Error Display: chilled water switch 

Name: flow switch protection

Source of Error Signal: chilled water switch

Description: When the chilled water flowing through the unit is not sufficient, the flow switch protection will occur. The error LED of system 1 and system 2 (dual system) will light and all the compressors, chilled water pumps and cooling water pumps will stop immediately. The malfunction information is shown on the wired controller. It can be reset automatically.

Gree Chiller Error Code List
Gree Chiller Error Code List

Error Display: cooling water switch 

Name: chilled water switch

Source of Error Signal: chilled water flow switch

Description: When the cooling water flowing through the unit is not sufficient, the flow switch protection will occur. The error LED of system 1 and system 2 (dual system) will light and all the compressors, chilled water pumps and cooling water pumps will stop immediately. The malfunction information is shown on the wired controller. It can be reset automatically.

Error Display: anti-freezing heat detector 

Name: anti-freezing protection

Source of Error Signal: anti-freezing heat detector

Description: If the sensor is wrong, the error LED of system 1 and system 2 (dual system) will light and all the compressors will stop immediately. The malfunction information is shown on the wired controller. The unit can be started up only after the malfunction is removed manually.

Error Display: heat detector of intake chilled water 

Name: sensor malfunction protection

Source of Error Signal: heat detector of intake chilled water

Description: If the sensor is wrong, the error LED of system 1 and system 2 (dual system) will light and all the compressors will stop immediately. The malfunction information is shown on the wired controller. The unit can be started up only after the malfunction is removed manually.

Gree Chiller Error Code List

Error Display: heat detector of outflow chilled water

Name: sensor malfunction protection

Source of Error Signal: heat detector of outflow chilled water

Description: If the sensor is wrong, the error LED of system 1 and system 2 (dual system) will light and all the compressors will stop immediately. The malfunction information is shown on the wired controller. The unit can be started up only after the malfunction is removed manually.

Error Display: heat detector of intake cooling water 

Name: sensor malfunction protection

Source of Error Signal: heat detector of intake cooling water

Description: If the sensor is wrong, the error LED of system 1 and system 2 (dual system) will light and all the compressors will stop immediately. The malfunction information is shown on the wired controller. The unit can be started up only after the malfunction is removed manually.

Error Display: heat detector of outflow cooling water 

Name: sensor malfunction protection

Source of Error Signal: heat detector of outflow cooling water

Description: If the sensor is wrong, the error LED of system 1 and system 2 (dual system) will light and all the compressors will stop immediately. The malfunction information is shown on the wired controller. The unit can be started up only after the malfunction is removed manually.

Error Display: superheat

Name: superheat protection

Source of Error Signal: heat detector of outflow cooling water

Description: When the outflow cooling water temperature is higher than the  setting value, the superheat protection will occur. The error LED of system 1 and system 2 (dual system) will light and all the compressors will stop immediately. The malfunction information is shown on the wired controller. In that case, only when the outflow cooling water temperature is lower than the setting value, the malfunction can be removed by manual resetting.

Error Display: anti-freeze

Name: anti-freezing protection

Source of Error Signal: anti-freezing heat detector

Description: When the anti-freezing heat detector detects that temperature is lower than the setting value, the error LED of system 1 and system 2 (dual system) will light and all the compressors will stop immediately. The malfunction information is shown on the wired controller. In that case, only when the temperature is higher than the setting value, the malfunction can be removed by manual resetting.

Error Display: discharge high temperature

Name: discharge high temperature protection

Source of Error Signal: heat detector of discharge high temperature

Description: When the discharge temperature is higher than the setting value, the error LED of corresponding system will light and the corresponding compressors will stop immediately. The malfunction information is shown on the wired controller. In that case, only when the discharge temperature is lower than the setting value, the malfunction can be removed by manual

Error Display: phase sequence of power supply

Name: Phase sequence protection

Source of Error Signal: Lack phase protector

Description: When the phase sequence of the power supply is wrong or the power supply is lack of phase, the lack phase protection will occur and the error LED of system 1 and system 2 will light and all the compressors will stop immediately. The malfunction information is shown on the wired controller. The unit can be started up only after the malfunction is removed manually.

Error Display: low flow of cooling water 

Name: low flow protection of cooling water

Source of Error Signal: heat detector of inflow and outflow temperature for cooling water

Description: When the controller detects for successive 10min that the differential temperature between inflow and outflow cooling water is higher than the setting value, the error LED will light. The wired controller will display the information of insufficient cooling water flow, but the unit will not stop. The error can be removed automatically.

Error Display: low flow of chilled water

Name: low flow protection of chilled water

Source of Error Signal: heat detector of inflow and outflow temperature for chilled water

Description: When the controller detects for successive 10min that the differential temperature between inflow and outflow chilled water is higher than the setting value, c, but the unit will not stop. The error can be removed automatically

Error Display: high pressure sensor

Name: sensor malfunction protection

Source of Error Signal: high pressure sensor

Description: If the sensor is wrong, the error LED of system 1 and system 2 (dual system) will light and all the compressors will stop immediately. The malfunction information is shown on the wired controller. The unit can be started up only after the malfunction is removed manually.

Error Display: low pressure sensor

Name: sensor malfunction protection

Source of Error Signal: low pressure sensor

Description: If the sensor is wrong, the error LED of system 1 and system 2 (dual system) will light and all the compressors will stop immediately. The malfunction information is shown on the wired controller. The unit can be started up only after the malfunction is removed manually.

Error Display: discharge temperature sensor

Name: sensor malfunction protection

Source of Error Signal: discharge temperature sensor

Description: If the sensor is wrong, the error LED of system 1 and system 2 (dual system) will light and all the compressors will stop immediately. The malfunction information is shown on the wired controller. The unit can be started up only after the malfunction is removed manually.

Error Display: inspiratory temperature sensor 

Name: sensor malfunction protection

Source of Error Signal: inspiratory temperature sensor

Description: If the sensor is wrong, the error LED of system 1 and system 2 (dual system) will light and all the compressors will stop immediately. The malfunction information is shown on the wired controller. The unit can be started up only after the malfunction is removed manually.

Error Display: oil switch

Name: oil switch protection

Source of Error Signal: oil switch

Description: When the oil level of the compressor is too low, the oil level switch protection will occur. The corresponding error LED will light and the corresponding compressor will stop. The malfunction information is shown on the wired controller. The unit can be started up only after the malfunction is removed manually.

Error Display: differential pressure protection 

Name: differential pressure protection

Source of Error Signal: high pressure and low pressure sensor

Description: When it is detected that the differential pressure of the compressor is too low, the differential pressure protection will occur and the compressor will stop. The unit can be started up only after the malfunction is removed manually.

Error Display: heat detector of condenser outlet

Name: sensor malfunction protection

Source of Error Signal: heat detector of condenser outlet

Description: If the sensor is wrong, the error LED of system 1 and system 2 (dual system) will light and all the compressors will stop immediately. The malfunction information is shown on the wired controller. The unit can be started up only after the malfunction is removed manually.

Gree Water-Cooled Screw Chiller Manual PDF

Comments

Popular posts from this blog

Rittal Air Conditioner Error Codes

  System messages are shown on the display screen of the Comfort controller via the displays A1 to A20 and E0. Rittal Air Conditioner Error Codes Error Codes System message Possible cause A1 Enclosure door open Door open or door limit switch incorrectly positioned A2 Internal temperature of enclosure too high Cooling capacity inadequate/unit undersized. Error as a consequence of messages A03 to A17. A3 Filter monitoring Filter mat soiled A4 Ambient temperature too high/too low Ambient temperature outside of admissible operating range (+10°C to +60°C) A5 Icing hazard Operational display in case of icing hazard. A6 PSAH pressure-operated switch Ambient temperature too high A7 Evaporator coil Lack of coolant; sensor in front of or behind condenser defective. A8 Condensate warning Condensate discharge kinked or blocked A9 Condenser fan blocked or defective Blocked or defective A10 Evaporator fan blocked or defective Blocked or defective A11 Compressor Compressor overloaded A12 Condense...

Samsung DVM-S VRF Error Codes

  DVM Digital Variable Multi VRF Systems Error Codes Samsung DVM VRF Error Codes Error code related indoor unit: Error Codes Explanation E-101 Indoor unit communication error. Indoor unit can not receive any data from outdoor unit. E-102 Communication error between indoor unit and outdoor unit. Displayed in indoor unit. E-108 Error due to repeated address setting (When 2 or more devices has same address within the network) E-121 Error on indoor temperature sensor of indoor unit (Short or Open) E-122 Error on EVA IN sensor of indoor unit (Short or Open) E-123 Error on EVA OUT sensor of indoor unit (Short or Open) E-128 EVA IN temperature sensor of indoor unit is detached from EVA IN pipe E-129 EVA OUT temperature sensor of indoor unit is detached from EVA OUT pipe E-130 Heat exchanger in/out sensors of indoor unit are detached E-135 RPM feedback error of indoor unit's cleaning fan E-149 Error due to AHU master indoor unit sensor setting. E-151 Error due to opened EEV of indoor unit ...

Panasonic VRF AC Error Codes and Troubleshooting

  Indoor unit is detecting error signal from remote controller (and system controller). Panasonic Mini VRF AC Error Codes and Troubleshooting Error Codes Meaning E01 Error in receiving serial communication signal. E02 Error in transmitting serial communication signal. E03 Indoor unit is detecting error signal from remote controller. E04 Error in receiving serial communication signal. When turning on the power supply, the number of connected indoor units does not correspond to the number set. E06 Error of the outdoor unit in receiving serial communication signal from the indoor unit. E08 Indoor unit address setting is duplicated. E09 Remote controller address connector. E12 Starting auto address setting is prohibited. This alarm message shows that the auto address connector CN-A.ADD is shorted while other RC line is executing auto address operation. E15 Error in auto address setting. E16 Error in auto address setting. E20 No indoor unit is connected during auto address setting. E24 ...