Skip to main content

Carrier Cassette Air Conditioner Error Codes

 Carrier cassette fault codes; Once a failure occurs with the indoor unit in operation, the green unit LED flashes at intervals of 0.5 seconds. The fault code is deduced from the number of times the green LED flashes, blocking unit operation. Between one flash cycle and the next one, a pause of 5 seconds elapses.

Carrier Cassette Air Conditioner Fault Codes
Carrier Cassette Air Conditioner Fault Codes

Carrier Fault Codes and Troubleshooting

Once a failure occurs with the indoor unit in operation, the green unit LED flashes at intervals of 0.5 seconds. The fault code is deduced from the number of times the green LED flashes, blocking unit operation. Between one flash cycle and the next one, a pause of 5 seconds elapses.

Error CodesDescription
3Room air sensor fault
2Condensate discharge pump
4Indoor unit coil sensor fault
6Filter dirty
7Outdoor unit failure
10EEPROM corrupt
11Card serial number damaged
12Address / zone incomplete
13Gas flow distributor corrupt
14Outdoor air thermistor
Carrier Cassette Display of Selected Functions
Carrier Cassette Display of Selected Functions

 

Aircon will not start:

  • The main switch is switched OFF, place the switch in the ON position.
  • The fuses on the main switch are burnt out; replace the fuses. ( this operation need to be carried out by qualified personnel only).
  • Wait for 3 minutes: protection against frequent compressor cycling is ON.
  • Selected temperature is higher than the room temperature (or lower in the heating mode).

The unit emits unpleasant smells:

Unpleasant smells can accumulate on the air filters and then be dispersed into the room during air conditioner operation. Switch the unit OFF and contact an authorised service centre to have the filters cleaned. Restart unit in the ventilation (fan only) mode and open windows to change room air.

The unit makes strange noises:

Occasionally the unit makes strange noises at start-up, during operation or when it has stopped. These are generally due to the effect of temperature changes on the plastic parts.

Air conditioner is not supplying enough cooling (or heating):

  • Air cannot circulate freely.
  • Dirty filter reduces air quantity circulating.
  • Filter must be cleaned by skilled personnel only.
  • Doors and/or windows are open.
  • Fan speed has been set to ‘low’.
  • Air flow direction is not correct for optimum ventilation.
  • Selected temperature is not correct.

P (Green LED) indicator is flashing:

System malfunction. Contact service organisation after having ensured that:

  • Air circulation is not obstructed.
  • Outdoor unit coil is not obstructed and causing severe reduction of air circulation.
  • Condensate drainage tube is not obstructed.

As regards fault codes to be communicated to the after-sales

Q (Red LED) indicator is illuminated:

In the heating mode, the LED switches on to indicate an active defrost condition.

Periodical checks

Carrier Cassette Periodical Checks
Carrier Cassette Periodical Checks

Carrier Cassette Air Conditioner  MANUAL PDF

Comments

Popular posts from this blog

Rittal Air Conditioner Error Codes

  System messages are shown on the display screen of the Comfort controller via the displays A1 to A20 and E0. Rittal Air Conditioner Error Codes Error Codes System message Possible cause A1 Enclosure door open Door open or door limit switch incorrectly positioned A2 Internal temperature of enclosure too high Cooling capacity inadequate/unit undersized. Error as a consequence of messages A03 to A17. A3 Filter monitoring Filter mat soiled A4 Ambient temperature too high/too low Ambient temperature outside of admissible operating range (+10°C to +60°C) A5 Icing hazard Operational display in case of icing hazard. A6 PSAH pressure-operated switch Ambient temperature too high A7 Evaporator coil Lack of coolant; sensor in front of or behind condenser defective. A8 Condensate warning Condensate discharge kinked or blocked A9 Condenser fan blocked or defective Blocked or defective A10 Evaporator fan blocked or defective Blocked or defective A11 Compressor Compressor overloaded A12 Condense...

Samsung DVM-S VRF Error Codes

  DVM Digital Variable Multi VRF Systems Error Codes Samsung DVM VRF Error Codes Error code related indoor unit: Error Codes Explanation E-101 Indoor unit communication error. Indoor unit can not receive any data from outdoor unit. E-102 Communication error between indoor unit and outdoor unit. Displayed in indoor unit. E-108 Error due to repeated address setting (When 2 or more devices has same address within the network) E-121 Error on indoor temperature sensor of indoor unit (Short or Open) E-122 Error on EVA IN sensor of indoor unit (Short or Open) E-123 Error on EVA OUT sensor of indoor unit (Short or Open) E-128 EVA IN temperature sensor of indoor unit is detached from EVA IN pipe E-129 EVA OUT temperature sensor of indoor unit is detached from EVA OUT pipe E-130 Heat exchanger in/out sensors of indoor unit are detached E-135 RPM feedback error of indoor unit's cleaning fan E-149 Error due to AHU master indoor unit sensor setting. E-151 Error due to opened EEV of indoor unit ...

Panasonic VRF AC Error Codes and Troubleshooting

  Indoor unit is detecting error signal from remote controller (and system controller). Panasonic Mini VRF AC Error Codes and Troubleshooting Error Codes Meaning E01 Error in receiving serial communication signal. E02 Error in transmitting serial communication signal. E03 Indoor unit is detecting error signal from remote controller. E04 Error in receiving serial communication signal. When turning on the power supply, the number of connected indoor units does not correspond to the number set. E06 Error of the outdoor unit in receiving serial communication signal from the indoor unit. E08 Indoor unit address setting is duplicated. E09 Remote controller address connector. E12 Starting auto address setting is prohibited. This alarm message shows that the auto address connector CN-A.ADD is shorted while other RC line is executing auto address operation. E15 Error in auto address setting. E16 Error in auto address setting. E20 No indoor unit is connected during auto address setting. E24 ...