Skip to main content

American Standard AC Error Codes

 Variable Speed AccuLink Heat Pumps and Air Conditioners. Variable Speed Alert Codes;

American Standard AC Error Codes
American Standard AC Error Codes
Led Fault CodesSolutions
1 FlashAmbient Temp Sensor is out of range (open/shorted). Initiate a 15 minute forced Defrost after every 60 minutes of runtime.
2 FlashCoil Temp Sensor is out of range (open/shorted). Initiate a 15 minute forced Defrost after every 60 minutes of runtime.
3 FlashLow Pressure Switch is open. 3 flash goes away when/if LPCO closes.
4 FlashHard Lock Out (can only be cleared with power cycle). Occurs after 4th trip of LPCO.
5 FlashSoft Lock Out. 5 flash goes away after soft lockout periods expires.
6 FlashDefrost cycles too close together. Heating Short Cycle Fault triggers 6 flash and 5 flash codes. Follow Soft Lock Out sequence until Hard Lock Out (4 flash) or can clear if conditions no longer exists.
7 FlashIn Timed Defrost mode. Check Ambient sensor placement and verify SOV is operating properly. Implied sensor fault (calibration/range) set after defrost and reset after 15 minutes run time after defrost.
8 FlashIn Timed Defrost mode. Check Coil sensor placement and verify SOV is operating properly. Outdoor temperature is below -7'F
9 FlashLow Ambient Soft Lockout. Outdoor temperature dropped below 3F. (OFF at -7F/ON at 3F) Outdoor temperature is below -7'F
13 FlashFault with the external temperature sensor
17 FlashHigh pressure problem
Amber light onUnit requires refrigerant.
Green light onUnit is operating normally.
  1. Initiate Adaptive/Timed Defrost so long as Coil Temp Sensor is functional. Monitor actual time in defrost and add or reduce run time until next forced defrost based on achieving a 4 minute (+/- 1) defrost period.
  2. 1st LPCO trip results in a 15 minute soft lockout period.
  3. If both Coil Temp Sensor and Ambient Temp Sensor are failed, initiate a 15 minute forced defrost after ever 60 minutes of run time.
  4. Do not track if Y cycles off or if defrost takes 15 minutes (Max Time Override). Ambient Sensor reading is monitored at the end of defrost and should not deviate more than +/-5F. Ambient Sensor must report a lower temperature than the Coil Sensor immediately after defrost (Coil Sensor should always be higher than Ambient Sensor when defrost terminates).
  5. Do not track if Y cycles off or if defrost takes 15 minutes (Max Time Override). Coil Sensor reading is monitored at the end of defrost and reading must be less than Ambient Sensor after 15 minutes of run time
  6. Once ambient drops to -7F or lower, wait 5 minutes before soft lockout begins. During soft lock out the Y signal passes through to the X2 output. Resume operation when ambient temperature rises to 3F or higher and after a 15 minute soft lockout period expires.
  7. During a Hard Lockout, the X2 relay opens so that the Y signal does not pass though.

Fault Code Recovery

On power up, last 4 faults, if any, will be flashed on the red LED. The newest fault detected will flash first and the oldest last. There will be a 2 second delay between fault code flashes. Solid red LED error codes will not be displayed. The Green LED will be on solid during last fault recovery. At any other time the control is powered, the Green LED indicator light will operate as shown in Table 14 and the red LED will flash LitePort data (one flash) every 20 seconds.

Fault Code Reset

The last 4 fault codes can be erased from memory by powering up the control with “G” energized and then applying “R” to the “W1” terminal 3 times within 6 seconds. The control will acknowledge the reset by turning on the red LED for 2 seconds.

Troubleshooting: Compressor fails to start, Contactor check

Troubleshooting-Compressor fails to start, Contactor check
Troubleshooting-Compressor fails to start, Contactor check
Cooling Refrigeration Cycle
Cooling Refrigeration Cycle
Heating Refrigeration Cycle
Heating Refrigeration Cycle
Schematic Diagram
Schematic Diagram

American Standard AC Service Manual PDF

Comments

Popular posts from this blog

Rittal Air Conditioner Error Codes

  System messages are shown on the display screen of the Comfort controller via the displays A1 to A20 and E0. Rittal Air Conditioner Error Codes Error Codes System message Possible cause A1 Enclosure door open Door open or door limit switch incorrectly positioned A2 Internal temperature of enclosure too high Cooling capacity inadequate/unit undersized. Error as a consequence of messages A03 to A17. A3 Filter monitoring Filter mat soiled A4 Ambient temperature too high/too low Ambient temperature outside of admissible operating range (+10°C to +60°C) A5 Icing hazard Operational display in case of icing hazard. A6 PSAH pressure-operated switch Ambient temperature too high A7 Evaporator coil Lack of coolant; sensor in front of or behind condenser defective. A8 Condensate warning Condensate discharge kinked or blocked A9 Condenser fan blocked or defective Blocked or defective A10 Evaporator fan blocked or defective Blocked or defective A11 Compressor Compressor overloaded A12 Condense...

Samsung DVM-S VRF Error Codes

  DVM Digital Variable Multi VRF Systems Error Codes Samsung DVM VRF Error Codes Error code related indoor unit: Error Codes Explanation E-101 Indoor unit communication error. Indoor unit can not receive any data from outdoor unit. E-102 Communication error between indoor unit and outdoor unit. Displayed in indoor unit. E-108 Error due to repeated address setting (When 2 or more devices has same address within the network) E-121 Error on indoor temperature sensor of indoor unit (Short or Open) E-122 Error on EVA IN sensor of indoor unit (Short or Open) E-123 Error on EVA OUT sensor of indoor unit (Short or Open) E-128 EVA IN temperature sensor of indoor unit is detached from EVA IN pipe E-129 EVA OUT temperature sensor of indoor unit is detached from EVA OUT pipe E-130 Heat exchanger in/out sensors of indoor unit are detached E-135 RPM feedback error of indoor unit's cleaning fan E-149 Error due to AHU master indoor unit sensor setting. E-151 Error due to opened EEV of indoor unit ...

Panasonic VRF AC Error Codes and Troubleshooting

  Indoor unit is detecting error signal from remote controller (and system controller). Panasonic Mini VRF AC Error Codes and Troubleshooting Error Codes Meaning E01 Error in receiving serial communication signal. E02 Error in transmitting serial communication signal. E03 Indoor unit is detecting error signal from remote controller. E04 Error in receiving serial communication signal. When turning on the power supply, the number of connected indoor units does not correspond to the number set. E06 Error of the outdoor unit in receiving serial communication signal from the indoor unit. E08 Indoor unit address setting is duplicated. E09 Remote controller address connector. E12 Starting auto address setting is prohibited. This alarm message shows that the auto address connector CN-A.ADD is shorted while other RC line is executing auto address operation. E15 Error in auto address setting. E16 Error in auto address setting. E20 No indoor unit is connected during auto address setting. E24 ...