Skip to main content

Amana PTAC Air Conditioner Error Codes

 Package Terminal, Air Conditioner/Heat Pump. Amana Diagnostic Codes;

Amana PTAC R410A AC Error Codes

If there are no active failures or lockouts, the display will show a double dash, “- -”. If there is a code listed, see the unit “Diagnostic Codes” chart for a list of definitions.

Error CodesProblem
FPFreeze Protection Engaged. The room temperature measured by the wireless remote thermostat or indoor ambient thermistor active sensor falls below 40°F. No Action required. This setting will disengage when the room temperature rises above 43°F.
FdFront Desk switch is closed. All outputs are switched off. Open front desk switch to allow occupant unit operation.
EoUn-Configured Service Board - All operation held awaiting configuration. Enter Configuration Menu and set "C3" to "C" for coolers with electric heat or "H" for heat pumps.
EHEmergency Hydronic Engaged. The EHH switch is closed. Compressor is switched off. Open front emergency hydronic switch to allow occupant unit operation.
LSLoad Shedding Engaged. The LS switch is closed. Compressor and Electric heat is switched off. Open load shedding switch to allow occupant unit operation.
OnControl is configured to respond to a wired thermostat. No action if a wired thermostat is being used. Otherwise, see Configuration Settings.
oPOpen Door Lockout (DS1 & DS2 open; wireless). Close Room Door. Unit will not condition space with door open.
nPWindow Switch Lockout - (LS & INN open). Close Room Door or Window. Unit will not condition space with door or window open.
HPHeat Sentinel - (WIAT > u3). No action required. This setting will disengage when the room temperature falls.
UrUn-Rented Status (EHH & INN or wireless). Front Desk needs to set to Rented mode (if applicable).
F1Indoor Ambient Thermistor reads outside the range -20°F to 200°F & the wireless thermostat is not communicating to the unit control or Indoor Ambient Thermistor (IAT) without a wireless remote thermostat reads outside the range -20°F to 200°F. Replace black Indoor Ambient Thermistor or Wireless Remote Thermostat.
F2Wireless Remote Thermostat failure. Replace Wireless Thermostat.
F3Indoor Ambient Thermistor reads outside the range -20°F to 200°F. Replace black Indoor Ambient Thermistor.
F4Indoor Coil Thermistor either above or below operating tolerances. Replace Red Indoor Coil Thermistor.
F5Wireless Thermostat failure. Attempt to rebind Wireless Thermostat or Replace Wireless Thermostat.
F6Indoor Discharge Thermistor either above or below operating tolerances. Replace Yellow Indoor Discharge Thermistor.
FbLow Remote Battery Warning. Replace Batteries in Wireless Devices.
H1High Voltage Protection engaged. Power supply voltage is to high. Check for incoming power at correct voltage.
brBrown Out Protection engaged. Power was lost or voltage is low. Check for incoming power at correct voltage.
L6Discharge Air Too Hot. Clean Filter or Remove Air Blockage.
LCOutdoor Coil Thermistor temperature high. Clean Condenser Coils, Check Fan for fault. Code will reset after cleaning.
C2Indoor Air Recirculation. Large delta between thermostat and return. Clean Filter or Remove Air Blockage or Close Vent Door or Improve indoor to outdoor seal.
C5Outdoor Coil temperature too high for outdoor ambient temperature. Check for Blocked Outdoor Air or Clean Coil.
C1Indoor Coil is freezing up. Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube.
C3Indoor Coil is freezing up. Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube.
C4Indoor Coil froze up. Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube.
C6Poor Unit Performance. Check for blower motor, compressor, or electric heat operation.
C7Indoor Freezing Lockout (ICT - IAT > 20) +10 Min. Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube.

Amana Air Conditioner Troubleshooting:

Amana Air Conditioner Troubleshooting
Amana Air Conditioner Troubleshooting

Troubleshooting Chart for ECM Variable Speed Air Circulator Blower Motors

SymptomPossible Causes
Motor rocks slightly when startingThis is normal start-up for variable speed motor.
Motor won't start1. No movement. 2. Motor rocks, but won't start.
Motor oscillates up & down while being tested off of blowerIt is normal for motor to oscillate with no load on shaft
Motor starts, but runs erratically1. Varies up and down or intermittent. 2. "Hunts" or "puffs" at high CFM (speed).
Excessive noise1.Air noise. 2.Noisy blower or cabinet. 3."Hunts" or "puffs" at high CFM (speed).
Evidence of MoistureMotor failure or malfunction has occurred and moisture is present

 

Amana PTAC R410A AC Error Codes C1,C2,C3,C4,C5,C6,C8,C9,CD,D5,D7,D8,D9,DA,DB,DC,DF,R4,R5
Amana PTAC R410A AC Error Codes C1,C2,C3,C4,C5,C6,C8,C9,CD,D5,D7,D8,D9,DA,DB,DC,DF,R4,R5
DIAGNOSTIC CODES L6,LC,C2,C5,C1,C3,C4,C6,C7
DIAGNOSTIC CODES L6,LC,C2,C5,C1,C3,C4,C6,C7
Amana PTAC Wiring Diagram
Amana PTAC Wiring Diagram

Amana PTAC R410A AC Manual PDF

PACKAGE TERMINAL AIR CONDITIONER/HEAT PUMP Standard and Remote Applications with LED M70 Control Board and R-410A PDF

Comments

Popular posts from this blog

Rittal Air Conditioner Error Codes

  System messages are shown on the display screen of the Comfort controller via the displays A1 to A20 and E0. Rittal Air Conditioner Error Codes Error Codes System message Possible cause A1 Enclosure door open Door open or door limit switch incorrectly positioned A2 Internal temperature of enclosure too high Cooling capacity inadequate/unit undersized. Error as a consequence of messages A03 to A17. A3 Filter monitoring Filter mat soiled A4 Ambient temperature too high/too low Ambient temperature outside of admissible operating range (+10°C to +60°C) A5 Icing hazard Operational display in case of icing hazard. A6 PSAH pressure-operated switch Ambient temperature too high A7 Evaporator coil Lack of coolant; sensor in front of or behind condenser defective. A8 Condensate warning Condensate discharge kinked or blocked A9 Condenser fan blocked or defective Blocked or defective A10 Evaporator fan blocked or defective Blocked or defective A11 Compressor Compressor overloaded A12 Condense...

Panasonic VRF AC Error Codes and Troubleshooting

  Indoor unit is detecting error signal from remote controller (and system controller). Panasonic Mini VRF AC Error Codes and Troubleshooting Error Codes Meaning E01 Error in receiving serial communication signal. E02 Error in transmitting serial communication signal. E03 Indoor unit is detecting error signal from remote controller. E04 Error in receiving serial communication signal. When turning on the power supply, the number of connected indoor units does not correspond to the number set. E06 Error of the outdoor unit in receiving serial communication signal from the indoor unit. E08 Indoor unit address setting is duplicated. E09 Remote controller address connector. E12 Starting auto address setting is prohibited. This alarm message shows that the auto address connector CN-A.ADD is shorted while other RC line is executing auto address operation. E15 Error in auto address setting. E16 Error in auto address setting. E20 No indoor unit is connected during auto address setting. E24 ...

Vestel AC Error Codes and Troubleshooting

  Error Messages   are displayed, respectively by first the   Er   icon and then the special code (01, 02, …, 20, etc.) of the failure. In that case, do nothing to the air conditioner and contact with the Authorised Service.   Er11   and   Er13   are not error messages. If you see these messages, apply the steps under the following protection messages section. Vestel AC Error Code and Troubleshooting Error Codes Cause dF The icing on the outdoor unit is being defrosted. After the defrosting operation is accomplished, your air conditioner will continue to operate in the heating mode, the product should not be turned off while this mode is enabled. RE Make the arc control for your electrical wiring, if the problem is not fixed call for the service. If the problem comes out very frequently, contact with the authorised service. Sr In case of certain failures, in order to not to spoil you comfort, your air conditioner continues to operate despite the f...